Modèle: KNLE1-100
marque: Korlen
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Air
Installation: Fixed
Structure: Elcb
Poles Number: 2
Type: Circuit Breaker
Function: Conventional Circuit Breaker
Certification: Ce
Rated Worling Current: 63;80;100a
Frame: 100a
Maximum Operating Time: I△n T≤0.1s , 5i△n T≤0.04
Sensibility: Ac Type
Rated Working Voltage: 240/415v
Détails d'emballage: carton
productivité: 5000000PCS/Year
transport: Ocean,Land,Air
Lieu d'origine: Wenzhou; Zhejiang; Chine
Certificats : CE,CB;VDE;
Code SH: 8536200000
Hafen: Ningbo,ShangHai
Type de paiement: L/C,T/T,D/P,Paypal
RCBO est le disjoncteur de courant résiduel avec protection contre les surintensités. Fondamentalement, il remplit les fonctions de MCB et RCCB ensemble. Cela signifie qu'il peut être utilisé pour protéger la ligne contre la surcharge et le court-circuité ainsi que le changement peu fréquent de la ligne dans une situation normale.
Le disjoncteur de fuite de la série KNLE1-100 s'applique à la ligne allant jusqu'à 230 V pour une monophasé ou jusqu'à 400 V pour trois phases avec le courant nominal jusqu'à 63A pour agir comme une protection des fuites. Lorsque quelqu'un obtient un choc électrique ou le courant de fuite à la ligne dépasse la valeur stipulée, le disjoncteur pourrait automatiquement casser la puissance en 0,2 s pour protéger le corps et l'équipement.
Le disjoncteur de fuite de la série KNLE1-100 effectue la protection de surcharge et de court-circuit et effectue également la faible fréquence de commutation de circuit dans un état normal. Ce produit est conforme aux exigences des normes GB16917.1.
Disjoncteur de fuite de terre
Disjoncteur de fuite
Elcb
Frame class | 100A |
Rated working voltage | 240/415V |
Rated frequency | 50/60Hz |
Rated working current | 63,80,100A |
Rated residual operating current | 0.03,0.1A |
Rated residual un-operating current | 0.015,0.05A |
Sensibility | AC Type |
Maximum operating time | IΔn t≤0.1s , 5IΔn t≤0.04 |
Instant release type | C type |
Limiting value of un-operating current | 6In |
Rated limiting short-circuit current | 6000A |
Pole number | 1P+N,2P,3P,3P+N |
Mechanical life | 8000 |
Electric life | 4000 |
Sequence NO . |
Release |
Test current I/In |
Start state |
Tripping time |
Expected restlt |
1 | c | 1.13In | Cold state | t≤2h | Not tripping |
2 | c | 1.45In |
Start right after the serial NO . 1 test |
t<2h | Tripping |
3 | c | 2.55In | Cold state | 1s<t<120s | Tripping |
4 | c | 5In | Cold state | t≤0.1s | Not tripping |
5 | c | 10In | Cold state | t<0.1s | Trippi |
Groupes de Produits : Disjoncteur à courant résiduel avec protection contre les surcharges > Disjoncteur à courant résiduel KNLE1-63 avec protection contre les surcharges